Removal and Replacement 121
Removal and Replacement
10 Watch the BCC Fault LED (B in Figure 55). It should come on briefly and
then turn off. If the LED stays on and a buzzer sounds, the switch settings do
not match the settings on the peer BCC. For other solutions to a BCC fault,
see “Isolating Causes” in Chapter 4.
11 Tighten the locking screws (B in Figure 54).
12 Reattach the SCSI cable and terminator.
Caution The BCC must be replaced or a filler panel installed in the open
slot to ensure proper cooling for the disk system.